SURVEY REPORT

Report Name: Demo Report
Date: November 7, 2021
Contractor: Aerial Production Services


OVERVIEW

Aerial Production Services performed an Aerial Gas Leak Survey of Compressor Station and 3 Well Site Locations Outlined in the Report. The Gas Leak Survey identified 9 Total Methane Leaks. See Report Below for additional Details.

Name Anomaly Type Severity(Low) Severity(Medium) Severity(High)
Compressor Station Leak 1 4 0
Leak 1 0 0
None 0 0 0
Leak 3 0 0

Methodology

An Aerial Flight is conducted to find locate leak areas. Larger leaks are captured with the OGI system from the UAV. Smaller leaks that the TDLAS picks up on during the flight and a good OGI video cannot be obtained are captured during the Ground Scan.


Compressor Station Overview


Station Leak 1

Time Date Location/GPS Peak Reading(ppm.m) Anomaly Type Severity
11:27AM 11/07/2021 5432 Leak Medium

Station Leak 5

Time Date Location/GPS Peak Reading(ppm.m) Anomaly Type Severity
11:42AM 11/07/2021 40 Leak Low

No OGI Picture as Ground Scan Needs to be Completed


Crew Site Observations

Asset Name: Compressor Station
Beginning Time: 17:27:15 UTC
Surveyor Name: Drew Talley
Instruments Used: ICI Sensor Combo (OGI, RGB, TDLAS)
Instrument Make: ICI
Instrument Model: OGI Inspector Plus
Location:
Ambient Temperature: 53
Windspeed: 3 nnw.
Deviation from monitoring plan? No Deviation
End Time: 18:27:22 UTC
Leak(s) Detected: 5
Component(s) Location: See Report
Leak(s) Comment: See Report Leak Observations
Difficult to monitor: None, Outside Inspection Only
Unsafe to monitor: None
Repair Due Date: TBD

Leak 1: Condensate Tank. Consistent readings. Averaging approximately 3,000 ppm.m.
Leak 2: Separator. Consistent readings. Averaging 1,500 ppm.m
Leak 3: Unknown Equipment Type. Consistent readings. Averaging 2,300 ppm.m.
Leak 4: Exhaust Readings. Higher Methane readings within the area of the Compressor Exhaust. Saturating the area.
Leak 5: Unknown Equipment Type. Inconsistent readings. Very low readings. Sporadic.


Compressor Station Crew Flight Readings

Notes: Flight path covered all visible exterior equipment. The readings above are shown from the location of the UAV at time of recording (every .80 Seconds) and are not indicative of the location of the leak. The UAV with sensor stands off from the equipment on average of 15-20 meters. See Leak information for data that corresponds to each leak.



Leak 1

Methane Sensor Data Reading 2332 ppm.m


Crew Site Observations

Asset Name:
Beginning Time: 18:59:15 UTC 11/6/2021
Surveyor Name: Drew Talley
Instruments Used: ICI Sensor Combo (OGI, RGB, TDLAS)
Instrument Make: ICI
Instrument Model: OGI Inspector Plus
Location:
Ambient Temperature: 69
Windspeed: 7 wsw.
Deviation from monitoring plan? No Deviation
Leak(s) Detected: 1
Component(s) Location: See Report
Leak(s) Comment: See Report Leak Observations
Difficult to monitor: None, Outside Inspection Only
Unsafe to monitor: None
Repair Due Date: TBD
Resurvey Date: TBD
Requested Repair? No

Leak 1: Pipe Thread. Consistent readings. Averaging approximately 500 ppm.m.


Crew Flight Readings


Well Site Overview

Leak 1

Time Date Location/GPS Peak Reading(ppm.m) Anomaly Type Severity
1:55PM 11/08/2021 183 Leak Low

Leak 2

Time Date Location/GPS Peak Reading(ppm.m) Anomaly Type Severity
2:06PM 11/08/2021 186 Leak Low

Crew Site Observations

Asset Name:
Beginning Time: 19:51:23 UTC 11/8/2021
Surveyor Name: Drew Talley
Instruments Used: ICI Sensor Combo (OGI, RGB, TDLAS)
Instrument Make: ICI
Instrument Model: OGI Inspector Plus
Location:
Ambient Temperature: 69
Windspeed: 7 wsw.
Deviation from monitoring plan? No Deviation
End Time: 20:10:18 UTC 11/8/2021
Leak(s) Detected: 3
Component(s) Location: See Report
Leak(s) Comment: See Report Leak Observations
Difficult to monitor: None, Outside Inspection Only
Unsafe to monitor: None
Repair Due Date: TBD

Leak 2: WellHead Thread. Intermittent Leak. Small Average below 50 ppm.m
Leak 3: Unknown Equipment Leak. Continuous Leak. Average 35 ppm.m


Crew Flight Readings